Industrial Anderson Power 2007G1-NC-BK connector providing power transfer in renewable energy setups
Anderson Power Saf-D-Grid Connectors
Product Overview
The Anderson Power Saf-D-Grid connector system builds upon the proven contact technology of SB and Powerpole connectors, offering enhanced features for high-voltage DC or hybrid AC/DC systems. Designed to meet international safety requirements, Saf-D-Grid provides a safe and efficient power connection for devices carrying AC or DC current up to 30A and 600V, fitting within the footprint of an IEC 620 C13/C14. It enables greater power density by delivering more voltage and current than similarly sized IEC 60320 connectors, making it ideal for applications requiring reliable power in renewable and alternative energy systems.
Product Attributes
- Brand: Anderson Power
- Product Line: Saf-D-Grid
- Legacy: Builds on SB and Powerpole connector technology
- Certifications: UL 950, IEC 60950, UL 1977, CSA 22.2, UL 817, IEC 61984
- Material (Housings): High Temp Nylon 30% Glass, UL94 V-0, Halogen Free; Polycarbonate UL94 V-0
- Material (Springs): Stainless Steel
- Material (Contacts): Copper/Silver Plate
- Material (Shield): Copper/Tin Plate
- Material (Cable/Strain Relief): Thermoplastic UL94 V-2
- Environmental: RoHS compliant
Technical Specifications
| Specification | Saf-D-Grid 400V Series | Saf-D-Grid 300V Series |
|---|---|---|
| Voltage Rating (AC/DC) | Up to 600V | Up to 600V (AC), Up to 400V (DC) |
| Current Rating (UL 1977) | See Page 5 Table | See Page 5 Table |
| Wire Range | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) |
| Dielectric Withstanding Voltage | 3300V | 3300V |
| Operating Temperature | -4 to 176F (-20 to 105C) | -4 to 284F (-20 to 105C) |
| Contact Retention | 20 lb (89N) | 20 lb (89N) |
| Plug Latch Retention | 20 lb (89N) | 20 lb (89N) |
| Panel Latch Retention | 60 lb (267N) | 60 lb (267N) |
| Durability | 5,000 Cycles (no load) | 5,000 Cycles (no load) |
| Receptacle Max Wire Size | 10 AWG (4.0 mm) | N/A |
| Creep and Clearance | 7.0 mm min | 7.0 mm min |
| Max PCB Thickness (for PCB contacts) | 0.093" (2.4 mm) | N/A |
| Mechanical Shock (IEC 60512-4-6C) | 50g | 50g |
| Vibration (IEC 60512-4-6d) | 20g | 20g |
| AC Disconnect Voltage | 600V (UL) / 400V (IEC) | 600V (UL) / 400V (IEC) |
| DC Disconnect Voltage | 600V (UL) | 600V (UL) / 400V (IEC) |
| Fault Current Withstand (UL 467) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) | 14 AWG, 300V, 4s |
Key Features
- First Mate, Last Break Ground Contact: Ensures a safe earthing path before power contacts engage.
- Integral Latch: Prevents accidental unmating, safeguarding critical equipment.
- Hot Plug Rated: Suitable for current interruption of both electronic (capacitive) and electrical (resistive) loads.
- Touch Safe / Shock Protection: Minimizes contact with hazardous voltages, passing UL & IEC finger probe tests.
- Arcing Protection: Housings contain arcs during mating/unmating under load, enhancing personnel safety.
- IEC 620 C13/C14 Footprint: Compact design allowing for greater power density.
- Keying Configurations: Single keying for 400V series (DC focus, AC rated); Multiple mechanical keys for 300V series (AC focus, DC rated).
Cable Configurations
Available in North American, Metric, Universal, and IEC 60320 (C14 and C20) configurations, with various cable types (SJT, H05VV-F, H05V2V2-F) and lengths. Also available with color-coded options (Red, Blue) for specific IEC configurations.
Tooling
Anderson assembly tooling is required for UL, CSA & other safety agency compliance. Use of unapproved tooling will void connector warranty. Automated and hand tooling options are available.