power connection solutions featuring Anderson Power 2005V4 Saf D Grid connectors for AC DC systems
Anderson Power Saf-D-Grid Connectors
Product Overview
The Anderson Power Saf-D-Grid connector system builds upon the proven contact technology of SB and Powerpole connectors, offering enhanced features for higher voltage DC or hybrid AC/DC systems. Designed to meet international safety requirements, Saf-D-Grid connectors enable greater power density within the footprint of an IEC 620 C13/C14, safely and efficiently connecting devices carrying AC or DC current up to 30A and 600V. Key features include a first-mate, last-break ground contact for enhanced safety, an integral latch to prevent accidental unmating, hot plug rating for both electronic and electrical loads, touch-safe design with shock protection, and arc containment within housings. These connectors are ideal for applications requiring reliable power connections in systems using AC or DC, particularly in locations where renewable and alternative energy sources are utilized to maintain system uptime.
Product Attributes
- Brand: Anderson Power
- Product Line: Saf-D-Grid
- History: Builds on SB and Powerpole connector technology, introduced in 1953.
- Safety Standards Met: UL 950, IEC 60950, UL 1977, CSA 22.2, UL 817, IEC 61984.
- Certifications: UL recognized components (UL file # E26226), UL817 recognized or listed cord sets (UL file # E 343569), CNR (Canadian National Standards, C22.2 No. 182.3).
- Environmental Compliance: RoHS compliant, Halogen Free (for specific housings).
- Materials: High Temp Nylon 30% Glass (UL94 V-0), Polycarbonate (UL94 V-0), Stainless Steel, Copper/Silver Plate, Copper/Tin Plate, Thermoplastic (UL94 V-2).
- Color: Black (standard housing and overmold), Red/Blue available for specific cable configurations.
Technical Specifications
| Specification | Saf-D-Grid 400V Series | Saf-D-Grid 300V Series |
|---|---|---|
| Voltage Rating (AC/DC) | Up to 600V (UL), 400V (IEC) | Up to 600V (UL), 400V (IEC) |
| Current Rating (UL 1977) | See Page 5 Table | See Page 5 Table |
| Current Rating (IEC) | Up to 30A (varies by model and wire size) | Up to 25A (varies by model and wire size) |
| Disconnect Current Interrupt | 600V (UL), 400V (IEC) | 600V (UL), 400V (IEC) |
| Wire Range | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) |
| Operating Temperature | -20 to 105C (-4 to 284F) | -20 to 105C (-4 to 284F) |
| Contact Retention | 20 lb (89N) | 20 lb (89N) |
| Plug Latch Retention | 20 lb (89N) | 20 lb (89N) |
| Panel Latch Retention | 60 lb (267N) | 60 lb (267N) |
| Durability | 5,000 Cycles (no load) | 5,000 Cycles (no load) |
| Dielectric Withstanding Voltage | 3300V | 3300V |
| Creep and Clearance | 7.0 mm min | 7.0 mm min |
| Mechanical Shock | 50g (IEC 60512-4-6C) | 50g (IEC 60512-4-6C) |
| Vibration | 20g (IEC 60512-4-6d) | 20g (IEC 60512-4-6d) |
| Fault Current Withstand (UL 467) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) |
Models and Ratings (Examples)
| Series | Key Configuration | Wire Size | UL 1977 Rating (Amps) | IEC 61984 Rating (Amps) | Disconnect (UL/IEC) | Current Interrupt (UL/IEC) |
|---|---|---|---|---|---|---|
| SDG 300 Receptacle | A | 14 AWG | 35 | N/A | 25A / N/A | 20A / 20A |
| SDG 400V Flush Mount | N/A | 14 AWG | 20 | N/A | 20A / N/A | 20A / 20A |
| SDG 400V Ultra Short | C | 10 AWG | 30 | N/A | 30A / N/A | 30A / 30A |
| SDG 300V Key A | A | 14 AWG SJT | 16A | 16A | 300V / 300V | 300V / 300V |
| Saf-D-Grid 400V to C14 | N/A | 14 AWG SJT / 1.5mm H05VV-F | 15A / 10A | 15A / 10A | 250V / 250V | 250V / 250V |
| Saf-D-Grid 400V to C20 | N/A | 12 AWG SJT / 2.5mm H05VV-F | 20A / 16A | 20A / 16A | 250V / 250V | 250V / 250V |
Features
- First Mate, Last Break Ground Contact
- Integral Latch (T-Latch on Straight Plug)
- Hot Plug Rated
- Touch Safe / Shock Protection (Passes UL & IEC finger probe tests)
- Arcing Protection
- Compact footprint comparable to IEC 620 C13/C14
- Wide "T" Latch Plug design for easier access
2411220411_Anderson-Power-2005V4_C3095644.pdf