Specifications
Mfr. Part #:
2007G3-BK
Model Number:
2007G3-BK
Introduction

Anderson Power Saf-D-Grid Connectors

Product Overview

The Anderson Power Saf-D-Grid connector system builds upon the proven contact technology of SB and Powerpole connectors, offering enhanced features for DC power connections in higher voltage DC or hybrid AC/DC systems. Designed to meet international safety requirements, Saf-D-Grid connectors provide a safe and efficient power connection for both AC and DC currents, enabling greater power density within the footprint of an IEC 620 C13/C14. Key features include a first-mate, last-break ground contact for enhanced safety, an integral latch to prevent accidental unmating, hot-plug rating for current interruption, touch-safe design with shock protection, and arcing protection within the housings. These connectors are ideal for applications where renewable and alternative energy sources are critical for system uptime.

Product Attributes

  • Brand: Anderson Power
  • Product Line: Saf-D-Grid
  • Technology Base: Builds on SB and Powerpole contact technology
  • Certifications: UL 950, IEC 60950, UL 1977, CSA 22.2, UL 817, IEC 61984
  • Materials: High Temp Nylon 30% Glass (UL94 V-0, Halogen Free), Polycarbonate (UL94 V-0), Stainless Steel Springs, Copper/Silver Plate Contacts, Copper/Tin Plate Shield, Thermoplastic Cable/Strain Relief
  • Color: Black (unless otherwise specified)

Technical Specifications

Specification Saf-D-Grid 400V Series Saf-D-Grid 300V Series
AC Current Rating (Disconnect) Up to 30A / 600V (UL) Up to 30A / 600V (UL)
DC Current Rating (Disconnect) Up to 30A / 600V (UL) Up to 30A / 600V (UL)
AC Current Rating (Interrupt) Up to 30A / 400V (IEC) Up to 30A / 400V (IEC)
DC Current Rating (Interrupt) Up to 30A / 400V (IEC) Up to 30A / 400V (IEC)
Footprint Compatibility IEC 620 C13/C14 IEC 620 C13/C14
Contact Retention 20 lb (89N) 20 lb (89N)
Plug Latch Retention 20 lb (89N) 20 lb (89N)
Panel Latch Retention 60 lb (267N) 60 lb (267N)
Durability 5,000 Cycles (no load) 5,000 Cycles (no load)
Max Wire Size (Receptacle) 10 AWG (4.0 mm) 10 AWG (4.0 mm)
Wire Range 10 AWG to 18 AWG (0.75 mm to 5.5 mm) 10 AWG to 18 AWG (0.75 mm to 5.5 mm)
Dielectric Withstanding Voltage 3300V 3300V
Operating Temperature -4 to 176F (-20 to 105C) -4 to 284F (-20 to 105C)
Fault Current Withstand (UL 467) 14 AWG, 300V, 4s (10 AWG, 750V, 4s) 14 AWG, 300V, 4s (10 AWG, 750V, 4s)
Hot Plug Rated Yes Yes
Touch Safe / Shock Protection Yes (Passes UL & IEC finger probe tests) Yes (Passes UL & IEC finger probe tests)
Arcing Protection Yes Yes

Receptacle Models & Ratings

Series Key Configuration Wire Size UL 1977 Current Rating (Amps) IEC 61984 Current Rating (Amps) Disconnect (600V) Current Interrupt (300V/400V)
SDG 300 Receptacle A 14 AWG 35 N/A 25 20
SDG 300 Receptacle C 10 AWG 55 N/A 38 32
SDG 400V Flush Mount - 18 AWG 18 N/A 12 12
SDG 400V Flush Mount - 14 AWG 20 N/A 20 20
SDG 400V Ultra Short - 14 AWG 21 25 13 20
SDG 400V Ultra Short - 10 AWG 30 N/A 30 30
SDG 300V Ultra Short Receptacle A 14 AWG 20 25 20 20
SDG 300V Ultra Short Receptacle C 10 AWG 30 32 30 32

Cable Configurations (Examples)

Part Number Connector 1 Cable Type Connector 2 Length Voltage Rating (Disconnect) Current Rating Temperature Rating
2035KZ1-BK Saf-D-Grid 400V 12 AWG ST None 1m 600V 25A 105C
2047KK2-BK Saf-D-Grid 400V 2.5mm H05VV-F Saf-D-Grid 400V 2m 300V 25A 70C
2058KH3-BLUE-BK Saf-D-Grid 400V 12 AWG SJT / 2.5mm H05VV-F (BLUE) IEC 320 C20 (BLUE) 3m 250V 20A / 16A 70C
2351-1200-20 Saf-D-Grid 300V KEY B 12 AWG SJT None 2m 300V 20A 90C