power connectors Anderson Power 2007G3-NC-BK designed for hybrid AC DC systems and industrial
Anderson Power Saf-D-Grid Connectors
Product Overview
The Anderson Power Saf-D-Grid connector system builds upon the proven contact technology of SB and Powerpole connectors, offering enhanced features for higher voltage DC or hybrid AC/DC systems. Designed to meet international safety requirements, Saf-D-Grid connectors provide a safe and efficient power connection for both AC and DC currents, enabling greater power density within the footprint of an IEC 620 C13/C14. Key features include a first-mate, last-break ground contact, integral latch for secure connections, hot-plug rating, touch-safe design, and arc containment, making them ideal for renewable energy, alternative energy, and other demanding applications requiring reliable power connectivity.
Product Attributes
- Brand: Anderson Power
- Product Line: Saf-D-Grid
- Origin: Built on SB and Powerpole contact technology
- Certifications: UL 950, IEC 60950, UL 1977, CSA 22.2, UL 817, IEC 61984
- Material (Housings): High Temp Nylon 30% Glass, UL94 V-0, Halogen Free; Polycarbonate UL94 V-0
- Material (Springs): Stainless Steel
- Material (Contacts): Copper/Silver Plate
- Material (Shield): Copper/Tin Plate
- Material (Cable/Strain Relief): Thermoplastic UL94 V-2
- Compliance: RoHS compliant
Technical Specifications
| Specification | Saf-D-Grid 400V Series | Saf-D-Grid 300V Series |
|---|---|---|
| Voltage Rating (AC/DC) | Up to 600V (UL 1977/CSA 22.2), 400V (IEC) | Up to 600V (UL 1977/CSA 22.2), 400V (IEC) |
| Current Rating (UL 1977) | See Table on Page 5 | See Table on Page 5 |
| Current Interrupt Rating | 30A (UL 1977), 400V (IEC) | 30A (UL 1977), 400V (IEC) |
| Disconnect Rating | 30A (UL 1977), 600V (UL 1977/CSA 22.2) | 30A (UL 1977), 600V (UL 1977/CSA 22.2) |
| Wire Range | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) |
| Contact Retention | 20 lb (89N) | 20 lb (89N) |
| Plug Latch Retention | 20 lb (89N) | 20 lb (89N) |
| Panel Latch Retention | 60 lb (267N) | 60 lb (267N) |
| Durability | 5,000 Cycles (no load) | 5,000 Cycles (no load) |
| Max Wire Size (Receptacle) | 10 AWG (4.0 mm) | 10 AWG (4.0 mm) |
| Creep and Clearance | 7.0 mm min | 7.0 mm min |
| Max PCB Thickness | 0.093" (2.4 mm) (for PCB contacts only) | N/A |
| Mechanical Shock | 50g (IEC 60512-4-6C) | 50g (IEC 60512-4-6C) |
| Vibration | 20g (IEC 60512-4-6d) | 20g (IEC 60512-4-6d) |
| Dielectric Withstanding Voltage | 3300V | 3300V |
| Operating Temperature | -4 to 176F (-20 to 105C) | -4 to 284F (-20 to 105C) |
| Fault Current Withstand (UL 467) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) |
| Keying Configuration | Single keying configuration | Multiple mechanical keys |
Receptacle Connector Ratings and Approvals
| Series | Wire Size | UL 1977 | CNR | IEC 61984 | UL 1977 | CNR | IEC 61984 | Part Number Example |
|---|---|---|---|---|---|---|---|---|
| Disconnect (600V) | Current Interrupt (300V/400V) | |||||||
| SDG 300 Receptacle Key "A" | 14 AWG | 35A | 25A | N/A | 20A | 20A | N/A | 2316G |
| SDG 300 Receptacle Key "A" | 12 AWG | 35A | 25A | N/A | 20A | 20A | N/A | 2316G |
| SDG 300 Receptacle Key "B" | 14 AWG | 35A | 25A | N/A | 20A | 20A | N/A | 2326G |
| SDG 300 Receptacle Key "B" | 12 AWG | 35A | 25A | N/A | 20A | 20A | N/A | 2326G |
| SDG 300 Receptacle Key "C" | 10 AWG | 55A | 38A | N/A | 32A | 32A | N/A | 2336G |
| SDG 400V Flush Mount | 18 AWG | 18A | 12A | N/A | 12A | 12A | N/A | 2002 |
| SDG 400V Flush Mount | 16 AWG | 18A | 18A | N/A | 14A | 14A | N/A | 2002 |
| SDG 400V Flush Mount | 14 AWG | 20A | 20A | N/A | 20A | 20A | N/A | 2002 |
| SDG 400V Flush Mount | 12 AWG | 25A | 25A | N/A | 25A | 25A | N/A | 2002 |
| SDG 400V Flush Mount | 1.5mm H05VV-F | N/A | N/A | 16A | N/A | N/A | 16A | 2002 |
| SDG 400V Flush Mount | 2.5mm H05VV-F | N/A | N/A | 25A | N/A | N/A | 25A | 2002 |
| SDG 400V Short | 18 AWG | 18A | 12A | N/A | 12A | 12A | N/A | 2005 |
| SDG 400V Short | 16 AWG | 18A | 18A | N/A | 14A | 14A | N/A | 2005 |
| SDG 400V Short | 14 AWG | 20A | 20A | N/A | 20A | 20A | N/A | 2005 |
| SDG 400V Short | 12 AWG | 25A | 25A | N/A | 25A | 25A | N/A | 2005 |
| SDG 400V Short | 1.5mm H05VV-F | N/A | N/A | 16A | N/A | N/A | 16A | 2005 |
| SDG 400V Short | 2.5mm H05VV-F | N/A | N/A | 25A | N/A | N/A | 25A | 2005 |
| SDG 400V Ultra Short | 18 AWG | 35A | 25A | 13A | 12A | 12A | 12A | 2006 |
| SDG 400V Ultra Short | 16 AWG | TBD | TBD | N/A | TBD | TBD | N/A | 2006 |
| SDG 400V Ultra Short | 14 AWG | 21A | 13A | 25A | 20A | 20A | 20A | 2006 |
| SDG 400V Ultra Short | 12 AWG | 25A | 25A | N/A | 25A | 25A | N/A | 2007 |
| SDG 400V Ultra Short | 10 AWG | 30A | 30A | N/A | 30A | 30A | N/A | 2007 |
| SDG 400V Ultra Short | 1.5mm H05VV-F | N/A | N/A | 16A | N/A | N/A | 16A | 2006 |
| SDG 400V Ultra Short | 2.5mm H05VV-F | N/A | N/A | 25A | N/A | N/A | 25A | 2006 |
| SDG 400V Ultra Short | 4.0mm H05VV-F | N/A | N/A | 32A | N/A | N/A | 30A | 2007 |
Cable Configurations
Various cable configurations are available, including North American, Metric, Universal, and IEC 320/C14 and C20 interfaces, with options for single-ended or double-ended plug assemblies and different cordset lengths.
North American 600V Cable Configurations
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Disconnect (AC) | Current Interrupt (AC) | Current Rating | Max Temperature |
|---|---|---|---|---|---|---|---|---|
| 2031KZ1-BK | Saf-D-Grid 400V | 14 AWG ST | None | 1m | 600V | 400V | 16A | 105C |
| 2035KK2-BK | Saf-D-Grid 400V | 12 AWG ST | Saf-D-Grid 400V | 2m | 600V | 400V | 25A | 105C |
| 2038KK6-BK | Saf-D-Grid 400V | 10 AWG ST | Saf-D-Grid 400V | 6m | 600V | 400V | 30A | 105C |
Metric Cable Configurations
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Disconnect (AC/DC) | Current Interrupt (AC/DC) | Current Rating | Max Temperature |
|---|---|---|---|---|---|---|---|---|
| 2041KZ1-BK | Saf-D-Grid 400V | 1.5mm H05VV-F | None | 1m | 300V | 300V | 16A | 70C |
| 2047KK2-BK | Saf-D-Grid 400V | 2.5mm H05VV-F | Saf-D-Grid 400V | 2m | 300V | 300V | 25A | 70C |
| 2049KK6-BK | Saf-D-Grid 400V | 4.0mm H05V2V2-F | Saf-D-Grid 400V | 6m | 300V | 30A (Current Interrupt) | 32A (Disconnect) | 90C |
Universal Cable Configurations
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Disconnect (AC/DC) | Current Interrupt (AC/DC) | Current Rating (UL,CSA / IEC) | Temperature Rating |
|---|---|---|---|---|---|---|---|---|
| 2050KZ1-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm H05VV-F | None | 1m | 300V | 300V | 16A / 16A | 75C UL / 70C IEC |
| 2058KK2-BK | Saf-D-Grid 400V | 12 AWG SJT / 2.5mm H05VV-F | Saf-D-Grid 400V | 2m | 300V | 300V | 20A / 25A | 75C UL / 70C IEC |
Saf-D-Grid 400V to IEC 320 C14 Cable Configurations
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Voltage Rating Disconnect (AC) | Voltage Rating Current Interrupt (AC) | Current Rating (UL,CSA / IEC) | Temperature Rating |
|---|---|---|---|---|---|---|---|---|
| 2059KN1-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm H05VV-F | IEC 320 C14 | 1m | 250V | 250V | 15A / 10A | 70C |
| 2059KN3-RED-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm H05VV-F (RED) | IEC 320 C14 (RED) | 3m | 250V | 250V | 15A / 10A | 70C |
Saf-D-Grid 400V to IEC 320 C20 Cable Configurations
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Voltage Rating Disconnect (AC) | Voltage Rating Current Interrupt (AC) | Current Rating (UL,CSA / IEC) | Temperature Rating |
|---|---|---|---|---|---|---|---|---|
| 2050KH1-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm H05VV-F | IEC 320 C20 | 1m | 250V | 250V | 16A / 16A | 70C |
| 2058KH3-BLUE-BK | Saf-D-Grid 400V | 12 AWG SJT / 2.5mm H05VV-F (BLUE) | IEC 320 C20 (BLUE) | 3m | 250V | 250V | 20A / 16A | 70C |
300V North American Configurations (with Keys for AC Usage)
| Part Number | Connector 1 | Cable | Connector 2 | Cordset Length | Voltage Rating Disconnect (AC/DC) | Voltage Rating Current Interrupt (AC/DC) | Current Rating | Temperature Rating |
|---|---|---|---|---|---|---|---|---|
| 2352-1100-10 | Saf-D-Grid 300V KEY A | 14 AWG SJT | None | 1m | 300V | 300V | 16A | 90C |
| 2352-1112-20 | Saf-D-Grid 300V KEY A | 14 AWG SJT | Saf-D-Grid 300V KEY B | 2m | 300V | 300V | 16A | 90C |
| 2351-1200-30 | Saf-D-Grid 300V KEY B | 12 AWG SJT | None | 3m | 300V | 300V | 20A | 90C |
| 2350-1300-60 | Saf-D-Grid 300V KEY C | 10 AWG SJT | None | 6m | 300V | 300V | 30A | 90C |
2411220411_Anderson-Power-2007G3-NC-BK_C3095833.pdf