power connection solutions with Anderson Power 2002V4 designed to meet international safety standards
Anderson Power Saf-D-Grid Connectors
Product Overview
The Anderson Power Saf-D-Grid connector system builds upon the established contact technology of SB and Powerpole connectors, offering enhanced features for DC power connections in higher voltage DC or hybrid AC/DC systems. Designed to meet international safety requirements, Saf-D-Grid connectors provide a safe and efficient power connection for both AC and DC applications, enabling greater power density within the footprint of an IEC 620 C13/C14. Key safety features include a first-mate, last-break ground contact, integral latch for preventing accidental unmating, hot-plug rating for current interruption of various loads, touch-safe design with shock protection, and arcing protection within the housings. These connectors are ideal for applications where renewable and alternative energy sources are critical for maintaining system uptime.
Product Attributes
- Brand: Anderson Power
- Product Line: Saf-D-Grid
- Legacy: Builds on SB and Powerpole contact technology
- Certifications: UL 950, IEC 60950, UL 1977, CSA 22.2, UL 817, IEC 61984 (specific models)
- Material (Housings): High Temp Nylon 30% Glass, UL94 V-0, Halogen Free (2006G/2007G series receptacle); Polycarbonate UL94 V-0 (All Other Housings)
- Material (Springs): Stainless Steel
- Material (Contacts): Copper/Silver Plate
- Material (Shield): Copper/Tin Plate
- Material (Cable/Strain Relief): Thermoplastic UL94 V-2
- RoHS Compliant: Yes
Technical Specifications
| Specification | Saf-D-Grid 400V | Saf-D-Grid 300V Series |
|---|---|---|
| Contact Retention | 20 lb (89N) | 20 lb (89N) |
| Plug Latch Retention | 20 lb (89N) | 20 lb (89N) |
| Panel Latch Retention | 60 lb (267N) | 60 lb (267N) |
| Durability | 5,000 Cycles (no load) | 5,000 Cycles (no load) |
| Receptacle Max Wire Size | 10 AWG (4.0 mm) | N/A |
| Creep and Clearance | 7.0 mm min | 7.0 mm min |
| Max PCB Thickness | 0.093" (2.4 mm) | N/A |
| Mechanical Shock (IEC 60512-4-6C) | 50g | 50g |
| Vibration (IEC 60512-4-6d) | 20g | 20g |
| Voltage AC Disconnect (UL) | 600V | N/A |
| Voltage AC Disconnect (IEC) | 400V | N/A |
| Voltage AC Current Interrupt (UL) | 600V | 400V |
| Voltage DC Disconnect (UL) | 600V | 600V |
| Voltage DC Current Interrupt (IEC) | 400V | 400V |
| Wire Range | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) | 10 AWG to 18 AWG (0.75 mm to 5.5 mm) |
| Dielectric Withstanding Voltage | 3300V | 3300V |
| Operating Temperature | -4 to 176F (-20 to 105C) | -4 to 284F (-20 to 105C) |
| Fault Current Withstand (UL 467) | 14 AWG, 300V, 4s (10 AWG, 750V, 4s) | 14 AWG, 300V, 4s |
Receptacle Connector Ratings and Approvals (Partial List)
| Series | Wire Size | UL 1977 Rating (Amps) | IEC 61984 Rating (Amps) | Disconnect (600V) | Current Interrupt (300V/400V) |
|---|---|---|---|---|---|
| SDG 300 Receptacle Key "A" | 14 AWG | 35 | N/A | 25 | 20 |
| SDG 400V Flush Mount | 14 AWG | 20 | N/A | 20 | 20 |
| SDG 400V Ultra Short | 14 AWG | 21 | 25 | 13 | 20 |
| SDG 400V Ultra Short | 10 AWG | 30 | N/A | 30 | 30 |
Cable Configurations (Examples)
| Part Number | Connector 1 | Cable | Connector 2 | Length | Voltage Rating Disconnect (AC/DC) | Current Rating |
|---|---|---|---|---|---|---|
| 2031KZ1-BK | Saf-D-Grid 400V | 14 AWG ST | None | 1m | 600V | 16A |
| 2035KK2-BK | Saf-D-Grid 400V | 12 AWG ST | Saf-D-Grid 400V | 2m | 600V | 25A |
| 2041KZ1-BK | Saf-D-Grid 400V | 1.5mm H05VV-F | None | 1m | 300V | 16A |
| 2058KK3-BK | Saf-D-Grid 400V | 12 AWG SJT / 2.5mm H05VV-F | Saf-D-Grid 400V | 3m | 300V | 20A / 25A |
| 2059KN2-BLUE-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm2 H05VV-F (BLUE) | IEC 320 C14 (BLUE) | 2m | 250V | 15A / 10A |
| 2050KH3-RED-BK | Saf-D-Grid 400V | 14 AWG SJT / 1.5mm2 H05VV-F (RED) | IEC 320 C20 (RED) | 3m | 250V | 16A / 16A |
| 2352-1100-20 | Saf-D-Grid 300V KEY A | 14 AWG SJT | None | 2m | 300V | 16A |
| 2351-1200-60 | Saf-D-Grid 300V KEY B | 12 AWG SJT | None | 6m | 300V | 20A |
| 2350-1300-30 | Saf-D-Grid 300V KEY C | 10 AWG SJT | None | 3m | 300V | 30A |
2411220411_Anderson-Power-2002V4_C3095002.pdf