Compact Circuit Protector Eaton LUG3-3 offering 35 mm DIN rail mount and multiple amp configurations
Bussmann Series Compact Circuit Protector (CCP2) Disconnect Switches
The Bussmann series Compact Circuit Protector (CCP2) is a revolutionary, next-generation fused UL 98 branch circuit disconnect switch utilizing UL Class CF CUBEFuse with Class J electrical performance. Offering a significantly smaller footprint (up to 51% less space) compared to traditional fusible solutions, these switches provide a high 200 kA SCCR, enhancing panel and assembly SCCR. The 35 mm DIN-Rail mount CCP2 is available in 30, 60, and 100 amp configurations, with options for rotary operation for enhanced safety and application flexibility. The switch-only versions are direct replacements for earlier models, with compatible auxiliary contacts and PLC remote fuse indicators. Accessories like multi-wire lug kits, selector handles, auxiliary contacts, and PLC fuse monitors further extend application versatility.
Product Attributes
- Brand: Bussmann series (Eaton)
- Certifications: UL 98 Listed (Guide WHTY, File E302370), cULus to Canadian Standard 22.2 No. 4-04 (Guide WHTY7, File E302370), RoHS compliant, CE
- Material: Not specified
- Color: Not specified
- Origin: Not specified
Technical Specifications
| Product | Amps | Volts | SCCR | Poles | Mounting | Lockout/Tagout |
| Compact Circuit Protector (CCP2) | 30, 60, 100 A | 347 Vac (1-pole), 600 Vac (2- & 3-pole), 125 Vdc* | 200 kA RMS Sym., 100 kA DC | 1-, 2-, 3-poles | 35 mm DIN-Rail, Panel Mount | 1/4 lock |
| Compact Circuit Protector Base (CCP2B) | Not specified | Not specified | Not specified | Not specified | Not specified | Not specified |
| Class CC, UL supplemental and IEC 10x38 (CCP2) | Not specified | Not specified | Not specified | Not specified | Not specified | Not specified |
| Low profile Class CC and G, UL supplemental and IEC 10x38 (CCPLP) | Not specified | Not specified | Not specified | Not specified | Not specified | Not specified |
| UL 98 fused disconnect switches | 30 to 800 A | Not specified | Not specified | Not specified | Not specified | Not specified |
| UL 98 non-fused disconnect switches | 30 to 1200 A | Not specified | Not specified | Not specified | Not specified | Not specified |
| UL 508 non-fused disconnect switches | 16 to 80 A | Not specified | Not specified | Not specified | Not specified | Not specified |
| Enclosed UL 98 and UL 508 disconnect switches | 30 to 800 A (Fused UL 98), 30 to 1200 A (Non-fused UL 98), 16 to 80 A (Non-fused UL 508) | Not specified | Not specified | Not specified | Not specified | Not specified |
*Switch amp rating and installed fuse amp rating dependent.
2411192335_EATON-LUG3-3_C3217415.pdf