High current Anderson Power 3-6035P1-BK connector with UL 1977 CSA certifications and electrical connection
Product Overview
The SB 120 connector series offers robust solutions for high-current applications up to 240 Amps. Designed for versatility, these connectors feature color-coded, mechanically keyed housings to prevent accidental cross-mating and identify different circuits. They accommodate wire sizes from 10 to 1 AWG (5.3 to 42.4 mm) and offer options for extended range contacts, chemical resistance, and panel mounting. Suitable for a wide range of industrial environments, the SB 120 connectors are built for durability and reliable electrical performance.
Product Attributes
- Brand: SB
- Contact Plating: Silver (Ag)
- Housing Materials: Standard Plastic Resin (Polycarbonate), Chemical Resistant Resin (Polycarbonate / PBT blend)
- Contact Retention Spring Material: Stainless Steel
- Housing Flammability Rating: UL94 V-0
- Glow Wire Rating: 960C (GWFI) / 800C (GWIT)
- Contact Termination Methods: Crimp (Wire Contacts), Hand Solder (Wire Contacts), Wrench / Socket (Busbar Contacts Only)
- Environmental Sealing (with Boots): IP64
- Touch Safety (with Wire Contacts): IEC 60529 IP10 (unmated)
- Finger Safety (Mated Only): IEC 60529 - IP20
- Certifications: UL 1977, CSA
Technical Specifications
| Specification | Value | Details |
|---|---|---|
| Product Series | SB 120 | Connectors |
| Maximum Amperage Rating (UL) | 240 Amps | With Extended Range Contacts (1 AWG) |
| Wire Size Range | 10 to 1 AWG (5.3 to 42.4 mm) | For Wire Contacts |
| Mated Length | 104.6 mm (4.12 inches) | - |
| Housing Dimensions (Approx.) | 63.5 mm (2.50 inches) Length, 37.6 mm (1.48 inches) Width | - |
| Operating Temperature (Standard) | -20C to 105C (-4F to 221F) | - |
| Operating Temperature (Chemical Resistant) | -40C to 105C (-40F to 221F) | - |
| Mating Cycles (No Load by Plating) | 10,000 Avg. | Silver (Ag) Wire and Busbar Contacts |
| Voltage Rating (AC/DC Steady State) | 400 V | - |
| Voltage Rating (AC/DC Operational) | - | - |
| Breaking Capacity - AMP Rating / Cycles | 120 Amp / 10 Cycles | - |
| Voltage Rating (Breaking Capacity) | 220 VDC | - |
| Wire Size Tested (UL) | 1 AWG | - |
| Contact Series Tested | 1323 | - |
| Cycle Life (IEC 60512 Test 9a) | 5,000 Cycles | - |
| Mechanical Strength (Impact) | IEC 60512-5 @ 29.5 Inches - Dropped 8 Times | - |
| Current Rating (Amperes) UL 1977 | 240 (Wire-to-Wire, 1 AWG) | - |
| Current Rating (Amperes) UL 1977 | 120 (Wire-to-Busbar, 2 AWG) | - |
| Voltage Rating AC/DC UL 1977 | 600 V | - |
| Dielectric Withstanding Voltage | 2,200 Volts AC | - |
| Avg. Mated Contact Resistance | 5 m | 5 1/2 of 2 AWG Wire |
| Hot Plug Current Rating | 250 Amps | 250 cycles at 120V DC 60A |
| Wire Entrance Diameter (Max) | 15.240 mm (0.600 inches) | - |
| Creepage / Clearance per IEC 60950-1 | 4.10 mm | Unmated & Mated |
| Standard Housings (Part Numbers) | - |
|
| Chemical Resistant Housings (Part Numbers) | - |
|
| Silver Plated Wire Contacts (Part Numbers) | - |
|
| Silver Plated Busbar Contacts (Part Numbers) | - |
|
| Accessories | - |
|
2412041134_Anderson-Power-3-6035P1-BK_C20918597.pdf