Versatile Anderson Power 134G1 connector featuring genderless design and color coded mechanical keys
Product Overview
Anderson Power Products (APP) SB50 connectors, pioneered in 1953, set the standard for two-pole DC power distribution and battery connections. These connectors feature a one-piece plastic housing with stainless steel springs to secure low-resistance contacts. They accommodate wire sizes from #16 (1.5 mm) to #6 (13.3 mm) and are available in standard and chemical-resistant housing options. Key features include genderless design, color-coded mechanical keys for polarization, low-resistance silver or tin-plated copper contacts, and UL rating for hot-plugging. The SB50 series offers versatility with wire, PCB, and busbar contact options, making it suitable for a wide range of applications requiring reliable DC power distribution and battery connections.
Product Attributes
- Brand: Anderson Power Products (APP)
- Series: SB50
- Housing Material (Standard): Polycarbonate
- Housing Material (Chemical Resistant): Polycarbonate / PBT blend
- Contact Spring Material: Stainless Steel
- Contact Base Material: Copper Alloy
- Contact Plating: Silver (Ag) or Tin (Sn)
- Housing Flammability Rating: UL94 V-0
- Certifications: UL 1977, CSA
Technical Specifications
| Specification | Value | Notes |
|---|---|---|
| Electrical Current Rating (UL 1977 Wire to Wire, 6 AWG) | 120 Amperes | |
| Electrical Current Rating (CSA Wire to Wire, 6 AWG) | 50 Amperes | |
| Electrical Current Rating (UL 1977 Wire to PCB, 6 AWG) | 50 Amperes | |
| Voltage Rating (UL 1977 AC/DC) | 600 Volts | |
| PCB Connector Recommended Voltage (IEC 60950-1 Table 2L) | Mini Vert. Contact: 522V, Mini Horiz. Contact: 504V, Standard Contact: 950V | |
| Dielectric Withstanding Voltage | 2,200 Volts AC | |
| Avg. Mated Contact Resistance (Milliohms) | Wire: 0.200, PCB: 0.500 | |
| UL Hot Plug Current Rating (250 cycles at 120V DC) | Wire-wire: 50A, PCB-wire: 40A (Vertical Mini Powerclaw) | |
| Wire Size Range (Wire Contacts) | 16 to 6 AWG (1.3 to 13.3 mm) | With Bushings |
| Max. Wire Insulation Diameter | 0.440 in. (11.200 mm) | |
| Operating Temperature (Standard Housing) | -20 to 105C (-4 to 221F) | |
| Operating Temperature (Chemical Resistant Housing) | -40 to 105C (-40 to 221F) | *Chemical resistant material not available for PCB guide housings |
| Mating Cycles (No Load) | Silver Plated: 10,000, Tin Plated: 1,500 | Wire and PCB Contacts |
| Avg. Mating / Unmating Force (Lbf./N) | Wire to Wire Low Force: 10/44, Wire to Wire High Force: 15/67, Standard Powerclaw to Wire: 15/66, Mini Powerclaw to Wire: 8/36 | |
| Max PCB Thickness (Plated Through Hole) | Standard: 0.15 in. [0.381mm], Mini: 0.25 in. [0.635mm] | |
| Min. Contact / Spring Retention Force (Lbf./N) | Wire Housing: 50/222 | |
| Min. Creepage / [Clearance] Distance (in./mm) | Standard Powerclaw: 0.374/9.5, Mini Vert. Powerclaw: 0.213/5.4, Mini Horz. Powerclaw: 0.205/5.2 | |
| Mechanical Shock | 50gs | MIL-STD-202, Condition A |
| Vibration (High Frequency) | 10gs | MIL-STD-202, Condition A |
| Contact Termination Methods | Crimp (Wire Contacts), Hand Solder (Wire and PCB Contacts), Solder Dip (PCB Contacts), Wave Solder (PCB Contacts), Wrench / Socket (Busbar Contacts) | |
| Protection (Touch Safety with Wire Contacts) | IP10 | IEC 60950-1 |
Based on: 105C rated or better cable of the largest size, properly calibrated APP recommended tooling, and a 25C ambient temperature. UL rating not to exceed the maximum operating temperature. CSA rating below a 30C temperature rise.
Limited by the thermal properties of the connector plastic housing.
Use APP recommended tooling only. Alternate tools may adversely affect the performance of our connectors along with UL and CSA recognition.